What does "tech ventilation linking scenario for percent served by heat tech...?
What does "tech ventilation linking scenario for percent served by heat tech [2] does not match preceding techs" mean?
This is an error message that comes up when there are incompatible heating or cooling systems defined in a building set. This can occur when one building is modeled with linked heating (a heating system requiring a fan to deliver the heat; e.g., furnace, fan coil, or AHU) with one served by an unlinked heating system (no fan required ; e.g., radiator or baseboard system) together in the same building set. The situation can be remedied by separating the buildings into distinct building sets. For more information about allowable HVAC combinations, refer to Appendix I of the FEDS User's Guide.