Custom EPW files may be created by experienced users and imported using the "Import EPW File" option. There is also an option in FEDS version 8 that allows users to view and alter the weather data (e.g., drybulb temperature, relative humidity, atmospheric pressure, and sky clearness). This is presently intended to allow users to make weather adjustments to be used when calibrating a model to conditions for a specific base year. Contact FEDS support for more information.
Yes. FEDS now provides an option to import additional weather station data. An "Import EPW Weather File" feature enables users to access the growing number of weather station data representing many locations globally, as well as more recent records of typical climate data, and even data covering specific time periods or energy modeling scenarios. All data must be in standard EPW file format. Refer to the FEDS User’s Guide for more information.
Normal/typical plug loads are accounted for (inferred) automatically within FEDS. These values can be viewed and/or changed from the miscellaneous equipment inputs in maximum detail display. The data is based on major end-use load surveys for typical plug load levels and accounts for the typical levels of equipment loads in a given use-area type. For example, for an office building this will account for typical levels of things, such as computers, printers, copiers, clocks, vending machines, coffee makers, and kitchenette equipment.
During a month that has been identified as seasonally unoccupied (also referred to as non-operating), FEDS assumes zero occupancy, all lights are off (except exit signs), and the cooling system is shut down. Heating is operated at a reduced level generally for the purpose of preventing the pipes from freezing (temperature kept at low setpoint specified by the unoccupied season thermostat setting). General plug loads are assumed to be non-operational, as are most motors (although this may be overridden by specifying monthly motor load factors).
Unoccupied hours or day types of occupied months are those periods during which there is reduced occupancy of the building. These are referred to as low occupancy periods in FEDS. For a typical commercial facility this might occur during the night and on weekends. A small number of occupants might be present (though less than during normal operating hours), and all energy systems remain active although they may operate at reduced levels. The operation of HVAC, lighting, plug loads, and motors are all controlled by inputs such as thermostat setpoints (enabling temperature setback), ventilation control mode, and utilization/load factors.
Full 24-hour occupancy can be specified for any day type by entering the same start and end hours (except 0 and 2400). For unoccupied day types enter 0 for both start and end times (or leave them blank). Note: if you do not specify occupancy hours, they will remain blank and FEDS will model the buildings as though they are unoccupied (reduced occupancy). Shortcut buttons are available on the standard occupancy inputs screen to make specifying continuously occupied and unoccupied day types easier.
Choose a weather station that most closely represents the weather at your location. Most times it will be a city in the same state as you, but can be in a neighboring state, or in some instances in another region altogether. When specifying the zip code of the site or building(s), FEDS will recommend a weather station that offers the most similar weather to your location.
inking two distinct building sets together allows greater flexibility in modeling complex building geometries or uses. Linked buildings are designed to model two buildings that share a common wall or are stacked on top of one another. Specifying that the buildings are linked directs FEDS to automatically (based on the geometry information for each building) determine the wall area (or roof/ceiling area) that is shared, and thus not exposed to exterior conditions. It essentially calculates the portion of each buildings shell that is an adiabatic surface (i.e., does not experience conductive heat transfer) and does not receive solar gains. It uses this information in load calculations to appropriately account for the impact of the buildings being connected. There are some rules, however, that must be satisfied in order to link building sets. First, both sets must contain the same number of buildings so that a direct one-to-one linking is achieved. Second, both sets must have the solar normalization turned off (calculate solar gains by facing direction). Also, FEDS currently does not model cantilevered buildings so for top/bottom linking, the N/S and E/W lengths of the top building must not be greater than the corresponding lengths of the bottom building.
Prototype buildings in FEDS are modeled as basic rectangular blocks, with the actual geometry calculated based on the total floor area, number of floors, floor-to-floor height, and aspect ratio. However, additional geometries can be modeled by using the linked building approach or through the advanced geometry inputs, which allow modification to underlying parameters including window/wall/roof/floor areas and conditioned air volumes.
Variable occupancy is an improved approach to the seasonal occupancy option which allows users to specify that certain months are non-operating (e.g., schools may be shut down over summer break). Variable occupancy also offers greater flexibility by allowing users to specify the percent of days within specific months which follow the general occupancy and operation schedule defined in the standard occupancy inputs. One hundred percent indicates the building or use area operates all days of that type during the month according the standard schedule. Zero percent indicates the building (use area) is either non-operating (shut down) or in a low occupancy state (occupied at the low occupancy and equipment use level) for all days of that type during the month. For any value between 0% and 100%, FEDS will multiply that value by the actual number of days of that type in the month and model the resulting number of days (rounded to the nearest whole day) as operating according to the standard schedule. The remainder of the days of that type in the month will be deemed either non-operating or at low occupancy (depending on the selection of non-operating period status type). As a convention, FEDS will model the first X days in the month as occupied and operating to the standard schedule, and the remaining days of that type in the month as non-operating or at low occupancy. The variable occupancy capability provides significant modeling flexibility and is particularly useful in modeling occupancy and building operation that varies within the course of a month, such as for National Guard or Reserve buildings that may only be heavily occupied on certain weekends through much of the year.
Another option for even greater control over building and use-area operation and occupancy (for each hour of the year) is also available. Contact FEDS Support for more information if interested in using this approach.
FEDS allows a negative value for percentage of heat to the conditioned space. For example, if the equipment has a COP of 2.0 and operates with an exterior condenser, then -200 should be entered for this value and the capacity should be half the actual rated capacity. (This will result in heating an amount equivalent to 200% of the unit's consumption as being rejected outside.)
The advanced geometry inputs allow for more flexibility in modeling non-standard building geometries compared to the linked building approach. When accessing the advanced geometry inputs, the user may specify or alter a number of geometric parameters for each zone of the building to customize the resulting model. For example, the exterior wall areas and window areas can be specified for the north, east, south, and west sides of each zone. Additionally, roof, floor, footprint areas, exterior perimeter length, and conditioned air volume can be specified for each zone. These adjustments provide users with the ability to model a number of more complex geometries, such as individual parts of a strip mall complex or varying window fractions for different sides of a building, with greater accuracy than through other means. The option can be accessed via the button on the regular geometry inputs screen.
Solar normalization is used when the orientation of a single building is unknown, does not align with N/S/E/W directions, or when there are multiple buildings of differing orientations in a building set. It can be used to avoid biasing the solar gains calculation by normalizing the exterior wall, window, and roof areas, such that the resultant loads are roughly the average of two buildings: one with an east/west orientation and one with a north/south orientation. FEDS can be set to "ignore facing directions" to use solar normalization.
The aspect ratio is used to define the geometric orientation of the buildings in a building set. It is a ratio of length to width and is calculated by dividing the typical north-facing length by the typical east-facing length.
FEDS now offers 1.116 weather station data locations, primarily from a TMY3 and CWEC sources. From this data it derives such information as heating and cooling design day conditions, hourly temperature, clearness, and humidity profiles for a typical meteorological year. See Appendix D of the FEDS User's Guide for more information.
The typical FEDS user will not have detailed information available regarding plug load levels in order to adequately model them and will need to rely on the inferred values. However, miscellaneous equipment records may be modified or added if a load is unusual or atypical of the use-area type, or has an extremely large load (or one that sees extensive use) that is above and beyond what would be considered typical. Similarly, a user may want to reduce the capacity density for some areas deemed to have a lower load density than typical for that type of space, or even delete entire records when there is no equipment in use of a given type.
No. All occupancy hours must be specified by the user. Failing to do so will indicate to the model that the building is operating in the unoccupied mode each day during the week.