Normal/typical plug loads are accounted for (inferred) automatically within FEDS. These values can be viewed and/or changed from the miscellaneous equipment inputs in maximum detail display. The data is based on major end-use load surveys for typical plug load levels and accounts for the typical levels of equipment loads in a given use-area type. For example, for an office building this will account for typical levels of things, such as computers, printers, copiers, clocks, vending machines, coffee makers, and kitchenette equipment.
Weekday, Saturday, and Sunday hot water consumption values are determined using typical usage rates for a given use-area type, along with the number of occupants and occupancy schedule for each day type. Values are also adjusted according to such parameters as the presence or absence of showers and high efficiency fixtures.
FEDS assumes circulating (or loop) hot water systems serve entire buildings. Specifying a loop system for use-area 1 automatically identifies that it also serves use-area 2. Loop systems that only serve use-area 2 cannot be modeled, and the loop selection box is unnecessary and is disabled.
Storage capacity for hot water is calculated using the building type and building's design occupancy. For distributed tank systems, values are rounded up to the next increment of typical tank capacity.
No. If a building (or use-area) has any hot water available users should specify 100% of it is served by hot water. As long as there is hot water available in a space, occupants will utilize it even if it is not immediately accessible. The purpose of having the portion served input is to allow the FEDS user to specify entire buildings (or use-areas) within a building set that do not have any hot water. For example, for a building set consisting of 10 buildings in which two of the buildings have no hot water service, they would enter that two buildings (or 20%) for the portion of buildings in this set that have no water heating.
FEDS allows a negative value for percentage of heat to the conditioned space. For example, if the equipment has a COP of 2.0 and operates with an exterior condenser, then -200 should be entered for this value and the capacity should be half the actual rated capacity. (This will result in heating an amount equivalent to 200% of the unit's consumption as being rejected outside.)
For distributed tank systems, FEDS assumes commercial tanks are 80 gallons, while residential units are 50 gallons.
FEDS assumes loop (circulating) systems serve an entire building and, therefore, the number of tanks is inferred to be one for each building, regardless of the number of use areas present.
The typical FEDS user will not have detailed information available regarding plug load levels in order to adequately model them and will need to rely on the inferred values. However, miscellaneous equipment records may be modified or added if a load is unusual or atypical of the use-area type, or has an extremely large load (or one that sees extensive use) that is above and beyond what would be considered typical. Similarly, a user may want to reduce the capacity density for some areas deemed to have a lower load density than typical for that type of space, or even delete entire records when there is no equipment in use of a given type.