On the *.txs report, the electricity dollar values listed under the "Annual Installation Energy Use by Fuel Type" and "Annual Energy Use by Building Set and Fuel Type" pages include both energy and demand charges. To determine how much of that total cost is attributable to the energy vs. demand, the demand component (reported on the following page) may be subtracted from this total value.
Yes. All motors in the FEDS retrofit database meet current applicable EPAct and EISA efficiency standards that vary depending on parameters, such as motor horsepower, enclosure type, and speed.
Emissions factors are used and relate a quantity of pollutant emitted (e.g., tons of CO2) per unit of fuel burned. There are factors for each of the six pollutant types corresponding to each main fuel type. To estimate emissions, FEDS multiplies the consumption value for each fuel type by the appropriate emission factor. The emissions factors for certain fuel types, (for example electricity) can vary significantly depending on factors, such as plant type (coal, gas, nuclear, hydropower) and source fuel composition (e.g., sulfur content) such that state average values are applied based on the typical generation resource mix supplying that state.
The inputs may be accessed within the operational and control technologies section of the ventilation inputs screen. A number of technology and control parameters are available for each. A two-position or continuously modulated damper is required for some of these options.
The air leakage into a building is determined from the inferred or user-specified infiltration rate. The infiltration rate is the amount of outside air entering the building during periods when the ventilation system is either not operating or not supplying outside air (i.e., times when building is not under a positive pressure).
While FEDS models motor energy use, demand, and interactions with the HVAC system quite well, it is not a substitute for the MotorMaster+ software. MotorMaster+ contains extensive motor management and analysis capabilities that are found in no other software program. FEDS recommends general categories and performance levels of motors based on what is currently available, but does not specify particular manufacturers or special features. It is recommended that results of motor analyses from FEDS be used in MotorMaster+ to further refine and specify motor purchase requirements.
For example, the effect of the affinity laws on fan motors can have a significant impact in degrading the efficiency of an energy-efficient motor if it has less slip than the original motor. While it is true that many energy-efficient motors run faster than their standard efficiency counterparts, there are typically energy-efficient motors available with a full-load rpm equivalent to that of the motor it is replacing. FEDS does not account for the effect of speed on energy consumption in centrifugal loads, but assumes the user can find a motor with an equivalent slip as their current motor. MotorMaster+ is an invaluable tool to help users assess the impact of speed on energy consumption and finding the right motor for a given application.
Attractive NPVs, payback periods, and SIRs typically fall within certain ranges, which should always be positive. However, negative values are possible in a couple of instances and do not necessarily indicate an error. The first possibility is that the project is recommended for a technology or building component you identified as "replacement required". As such, FEDS will recommend the most cost-effective replacement option, but not require that it be cost effective. So, while it may be the best replacement option, it may exhibit seemingly nonsensical economic figures of merit. Similarly, if a building retrofit occurs due to central plant or thermal loop abandonment, it may also exhibit negative savings criteria. That simply means that the retrofit (e.g., replacing central steam service with an in-building boiler) was not cost effective when looking just at the building energy use and costs. But the value of abandoning the central plant and/or distribution loop (due to the accompanying reductions in thermal losses and O&M costs) provided a net positive gain when added to the negative savings at the building level. Thus, at the site level, taking the central plant and thermal loop savings into account, the net benefit is positive—but purely from the building perspective (reflected in the TXD and CSV reports) the change from steam to dedicated boiler was not cost effective. Reviewing the central plant and thermal loops section of the TXS report and looking for a positive abandonment value will provide additional detail on just how much of a net positive gain accrues do the abandoning the plant and/or loop.
The index code in following the existing technology description for a heating or cooling technology represents the technology record number. For example,{H2} indicates a heating technology is actually heating record #2 (as input in the user interface). This information can be valuable when dealing with heat/cool pairs with several heating and cooling records in a single building set.
The utilization factor represents the percentage of time during a particular period that the motor is operating. The load factor indicates the typical operating output of the motor as a percentage of rated output. For example, a 10-horsepower motor driving a 6-horsepower load and operating 50% of the time would have a load factor of 60% and a combined utilization/load factor of 30%.
FEDS allows the user to specify this information separately for occupied and unoccupied hours, either constant over the year, or varying from month to month. FEDS uses these values to calculate the hours of operation, and hence the consumption, and demand implications of each motor record. FEDS also calculates the heat output of the motors and its impact on the HVAC system.
Many motors in use today are oversized for the load they are driving, and some are grossly oversized. In such situations, the motor is driving a load equal to only a fraction of its rated capacity, and if too low the operating efficiency of the motor may suffer. Most importantly, when it's time to replace the motor, purchasing a motor with far excess capacity for its load will cost much more than a properly sized motor. Why spend more than necessary for the same (or even worse) level of service? FEDS understands t many motors may be over- (or under-) sized and allows the user to specify the required capacity of a motor, if known. FEDS will use the required capacity in order to select a replacement motor of the proper size and base its performance and cost calculations accordingly.
Section 432 of the Energy Independence and Security Act of 2007 (EISA 432) requires U.S. federal agencies to perform energy and water evaluations of their covered facilities on a recurring basis and report their performance via the Compliance Tracking System (CTS). The FEDS CTS report is provided to help agencies compile and format results from their FEDS analyses to facilitate this reporting requirement. Measures identified with buildings modeled in FEDS are categorized and summarized into the CTS Evaluation Upload Template (in an Excel spreadsheet format).
The Energy Resilience and Conservation Investment Program (ERCIP) report (*.ecp, otherwise known as the DD 1391) is a special form required by certain U.S. Department of Defense agencies in order to submit projects for ERCIP funding. The ERCIP report is designed to facilitate the form preparation and submittal process.
The ventilation end use inputs screen contains very basic information on the ventilation motors (total capacity and efficiency). The fan motors button simply enables a user to specify more detailed motor parameters by accessing the underlying fan motor inputs screen. From here, information, such as speed, enclosure type, voltage, vintage, and number of motors can be specified. It is important to realize that if any of this information has been entered, the fan motor inputs on the main ventilation screen will be inaccessible without first deleting the more detailed inputs.
The [Heating/Cooling] end use designation is used for existing heat pumps or heat/cool pairs. Because such technologies provide both heating and cooling, two rows are needed to describe them on the *.csv report. [HEATING/Cooling] indicates that the data on that row pertain to the heating technology (and overall economic impacts) while [Heating/COOLING] indicates that the data describes the cooling portion of the equipment (and no overall energy and economic data are shown).
Motor inference data and an extensive list of replacement motors (including performance and cost data) have been compiled from the MotorMaster+ software's extensive database of three-phase motors. MotorMaster+ was developed under the U.S. Department of Energy's Motor Challenge Program by the Washington State University Cooperative Extension Energy Program.
For heat/cool pairs (separate heating and cooling technologies), information may be listed for both retrofits to new, more efficient equipment and to a heat pump. In some cases, it may be cost effective to replace the heating equipment (or cooling only, or both) with a newer unit of similar type, as well as replace both heat and cool simultaneously with a heat pump system. All cost-effective options will appear on the *.csv report. The best option can be determined by comparing the sum of the individual heat and cool annualized total life-cycle costing savings with that of the combined heat/cool system (i.e., heat pump).
The installed capital cost listed at the very bottom of the *.txd report represents the actual total cost including materials, labor, taxes, and overhead. It is the actual cost that would be paid to complete a project. The installed cost value listed under the life-cycle costs savings section displays both the present and annualized values of the installed cost as used in the life-cycle cost analysis. The present value of the installed cost may be less than the installed capital cost if the study period for the analysis is less than the life of the new equipment. This can occur when the remaining life of the existing technology is less than the life of the retrofit technology. In this case, the cost of the retrofit technology is annualized over its full rated life, but only the annualized costs occurring during the remaining life of the existing equipment is discounted back to the analysis year and used for a fair cost/benefit comparison.