Custom EPW files may be created by experienced users and imported using the "Import EPW File" option. There is also an option in FEDS version 8 that allows users to view and alter the weather data (e.g., drybulb temperature, relative humidity, atmospheric pressure, and sky clearness). This is presently intended to allow users to make weather adjustments to be used when calibrating a model to conditions for a specific base year. Contact FEDS support for more information.
Yes. FEDS now provides an option to import additional weather station data. An "Import EPW Weather File" feature enables users to access the growing number of weather station data representing many locations globally, as well as more recent records of typical climate data, and even data covering specific time periods or energy modeling scenarios. All data must be in standard EPW file format. Refer to the FEDS User’s Guide for more information.
Yes. All motors in the FEDS retrofit database meet current applicable EPAct and EISA efficiency standards that vary depending on parameters, such as motor horsepower, enclosure type, and speed.
No. FEDS infers parameters based on the most likely current condition of a building and its equipment. Inferences for an 1820 vintage building will reflect the typical improvements and upgrades that have occurred over time.
FEDS was originally designed to model buildings with single, homogeneous heating and cooling technologies within each individual building. The portion of building set served inputs are available to specify whole buildings within a building set that are served by a given technology. If your building has more than one type of heating or cooling technology, there are a couple of options. If the majority of service is provided by one system, users might simply model that one as if it were the only system serving the building. If the occupants use portable space heaters, users could account for the energy consumed and heating service provided by representing them as a miscellaneous equipment record. If, on the other hand, one system does not dominate, it would be best to model the building as a pair of linked buildings, with one technology serving each portion. Or, if a major renovation is being contemplated, users might wish to model the building once as if it were served by one technology, and once by the other. Optimizing each case separately, the results will provide insights into which system type would be best for the building.
An option is also available that makes it possible to model multiple heating or cooling technologies serving the same building(s). To enable this feature, select the percentage of each building served option from the heating or cooling end use inputs. When this option is specified, FEDS will model the defined HVAC technologies as serving the specified portion served of each building in the building set.
If the building is newer than the rated life of the equipment in question, then the remaining life is equal to the difference of rated life and building age. If the building is older than the equipment's rated life, FEDS assumes that on average, equipment will be halfway through their life (but users can override this assumption and specify actual equipment vintage). Rated lives vary by equipment technology. Some examples of rated lives used in FEDS are:
envelope components (windows, insulation, etc.) – 40 years
lights – typically 25 years (Although the cost of replacing lamps and ballasts is figured into the analysis based on specific replacement intervals and hours of operation)
boilers – 40 years
furnaces – 20 years
chillers – 20 years
package AC units – 15 years
heat pumps – Air Source/15 years, Ground-Coupled/20 years
motors – 15 years
hot water heaters – electric, 12 years; gas, 10 years; distributed heat pump, 12 years; central heat pump, 15 years
While FEDS models motor energy use, demand, and interactions with the HVAC system quite well, it is not a substitute for the MotorMaster+ software. MotorMaster+ contains extensive motor management and analysis capabilities that are found in no other software program. FEDS recommends general categories and performance levels of motors based on what is currently available, but does not specify particular manufacturers or special features. It is recommended that results of motor analyses from FEDS be used in MotorMaster+ to further refine and specify motor purchase requirements.
For example, the effect of the affinity laws on fan motors can have a significant impact in degrading the efficiency of an energy-efficient motor if it has less slip than the original motor. While it is true that many energy-efficient motors run faster than their standard efficiency counterparts, there are typically energy-efficient motors available with a full-load rpm equivalent to that of the motor it is replacing. FEDS does not account for the effect of speed on energy consumption in centrifugal loads, but assumes the user can find a motor with an equivalent slip as their current motor. MotorMaster+ is an invaluable tool to help users assess the impact of speed on energy consumption and finding the right motor for a given application.
If the boiler serves only one building, select single building boiler as the equipment type and the fuel type that fires the boiler (natural gas, distillate oil, etc.). If the steam is piped in from a central boiler plant or purchased from offsite, select central steam as the fuel type and specify the equipment type as either a radiator, fan coil, or air handling unit using central steam or hot water (in-building equipment is a heat exchanger). For steam purchased from an off-site supplier, input a price for purchased central steam in the non-electric energy price inputs. For self-generated steam, create a central plant record, associated conversion equipment, and thermal loops within the central plant and thermal loops inputs.
Choose a weather station that most closely represents the weather at your location. Most times it will be a city in the same state as you, but can be in a neighboring state, or in some instances in another region altogether. When specifying the zip code of the site or building(s), FEDS will recommend a weather station that offers the most similar weather to your location.
FEDS contains a built-in database of building survey data and is able to infer a number of building parameters based on the small set of required inputs provided by the user. For example, FEDS uses information such as building type, location, floor area, and vintage to determine the most likely construction type and geometry. It uses similar information along with heating fuel type and cooling equipment, to determine the most likely heating technology and ventilation system parameters for a building. All inferences enable a user to model buildings without having intimate knowledge of the detailed engineering parameters. The resulting building prototype parameter values are statistically the most likely values based on the limited set of information provided. Of course, all inferred data may be easily overwritten by simply entering (locking) a value in the user interface screens.
FEDS draws upon a number of sources to determine inferable parameter values. Major sources include national building energy consumption surveys such as the Commercial Buildings Energy Consumption, Residential Energy Consumption Survey, large end-use studies such as the End-Use Load and Consumer Assessment Program, ASHRAE handbooks, building and equipment codes and standards, and manufacturers' data and extensive building audit and evaluation experience.
The number of heat or cooling equipment should be specified. For boilers or chillers, enter the number of boilers or chillers and not the number of air handling units or fan coil units. Similarly, for furnaces, packaged cooling units, and heat pumps specify the number of those devices. If the building is served by a fuel generated at a central plant (not within the building), specify the number of heat exchangers that transfers heat from the central distribution loop to the building loop.
A locked value, in terms of FEDS inputs, is one that the user has entered for an inferable parameter. This indicates to the model that this is a user-entered value and should not be updated (inferred). Clicking on the lock symbol can also lock a currently inferred value. When a value is locked, the lock icon will appear as a latched or closed lock. To unlock a value, simply click the icon again, changing it to an open or unlatched lock. This value will now be inferred the next time inferences are run.
This is an error message that comes up when there are incompatible heating or cooling systems defined in a building set. This can occur when one building is modeled with linked heating (a heating system requiring a fan to deliver the heat; e.g., furnace, fan coil, or AHU) with one served by an unlinked heating system (no fan required ; e.g., radiator or baseboard system) together in the same building set. The situation can be remedied by separating the buildings into distinct building sets. For more information about allowable HVAC combinations, refer to Appendix I of the FEDS User's Guide.
The utilization factor represents the percentage of time during a particular period that the motor is operating. The load factor indicates the typical operating output of the motor as a percentage of rated output. For example, a 10-horsepower motor driving a 6-horsepower load and operating 50% of the time would have a load factor of 60% and a combined utilization/load factor of 30%.
FEDS allows the user to specify this information separately for occupied and unoccupied hours, either constant over the year, or varying from month to month. FEDS uses these values to calculate the hours of operation, and hence the consumption, and demand implications of each motor record. FEDS also calculates the heat output of the motors and its impact on the HVAC system.
A dual-fuel heat pump is an electric air-source heat pump that uses another fuel source (natural gas, LPG, oil) for the auxiliary or backup heat (instead of electric resistance coils). It can be accomplished within a single integrated unit or pieced together by mating a standard air source heat pump with a furnace via a controller. The controller determines which unit to operate based on outside temperature, relative efficiencies, and cost of each fuel.
The heat/cool pair is a concept added to FEDS with the advent of considering heat pumps as replacements to conventional heating and cooling technologies. A heat/cool pair identifies to the model which heating and cooling technologies jointly serve a particular building or group of buildings in the building set and may be considered for joint replacement by a heat pump technology. In order to consider heat pumps or any other integrated heating and cooling technology as replacements for existing heating and cooling technologies, the heat/cool pairs must be defined. Baseline heat pump records are automatically paired (as long as their fuel type, equipment type, number of units, and vintages match) upon updating inferences, while all non-heat pump technologies must be paired manually.
A linked heating and cooling system is when the heating and/or cooling coil is integrated with the ventilation system, employing air as the distribution fluid (air handler, fan coil, packaged unit, furnace, etc.).
An unlinked heating and cooling system is when the ventilation system (if present) is separate from the heating coil, and heat is provided without requiring fan-powered air delivery. Unlinked heating technologies include radiators, baseboard electric, or infrared heaters.
Currently, FEDS assumes that all cooling is linked, with the exception of evaporative coolers, which are assigned a separate, special ventilation scenario. For more detailed information see Section 4.4.2 of the FEDS User's Guide.
Many motors in use today are oversized for the load they are driving, and some are grossly oversized. In such situations, the motor is driving a load equal to only a fraction of its rated capacity, and if too low the operating efficiency of the motor may suffer. Most importantly, when it's time to replace the motor, purchasing a motor with far excess capacity for its load will cost much more than a properly sized motor. Why spend more than necessary for the same (or even worse) level of service? FEDS understands t many motors may be over- (or under-) sized and allows the user to specify the required capacity of a motor, if known. FEDS will use the required capacity in order to select a replacement motor of the proper size and base its performance and cost calculations accordingly.
The crossover temperature is the outdoor air temperature at which a dual-fuel heat pump switches operation from the heat pump to the backup technology. This is typically the control methodology for these systems and can be entered or determined by FEDS. FEDS will calculate the optimal crossover temperature based on electric and backup fuel prices, heat pump performance and capacity vs. temperature, and furnace efficiency.
A separate heat/cool pair is a pair of heating and cooling technologies that are completely separate units, yet serve the same area/building (e.g., a furnace and separate package unit, or a boiler and a chiller). An integrated heat/cool pair is one in which the heating and cooling sources are packaged together in the same unit (e.g., a packaged cooling unit with integral gas burner or 'gas-pack' system). Identifying a heat/cool pair as integrated tells FEDS that individual heating and cooling replacements cannot be considered as a direct replacement.
Similar to the separate vs. integrated discussion for heat/cool pairs, a separate backup source for a dual-fuel heat pump indicates there is a separate furnace that is connected to the heat pump via a controller. A dual-fuel heat pump with integrated backup is a heat pump unit with a built-in gas or LPG auxiliary heat source. For modeling purposes, the only real difference is that FEDS will consider replacing the individual components (heat pump or backup furnace) of a separate dual-fuel heat pump in addition to replacing the entire system.
Thermostat dead band for heating represents the range of temperatures below the set point at which the thermostat does not call for heat. For example, at a 70-degree set point and a 2-degree dead band, the temperature will drop to 68 degrees before heating is activated, raising the temperature back to 70. It may also be referred to as the throttling range or differential. It operates similarly for cooling, allowing the temperature to rise a number of degrees equal to the dead band before cooling is activated.
FEDS now offers 1.116 weather station data locations, primarily from a TMY3 and CWEC sources. From this data it derives such information as heating and cooling design day conditions, hourly temperature, clearness, and humidity profiles for a typical meteorological year. See Appendix D of the FEDS User's Guide for more information.
Motor inference data and an extensive list of replacement motors (including performance and cost data) have been compiled from the MotorMaster+ software's extensive database of three-phase motors. MotorMaster+ was developed under the U.S. Department of Energy's Motor Challenge Program by the Washington State University Cooperative Extension Energy Program.