FEDS can be run on a machine connected to a network. In some circumstances FEDS can even be run remotely from a network computer or file share. However, because each network is different and interference and connectivity issues are possible, for the best performance (and to lower the risk of problems) it is recommended to run FEDS from a local machine.
Yes. All motors in the FEDS retrofit database meet current applicable EPAct and EISA efficiency standards that vary depending on parameters, such as motor horsepower, enclosure type, and speed.
Sometimes when the system or software crashes, certain files are locked in the system's memory which can cause strange or unstable behavior upon restarting. If this occurs, try quitting FEDS and restarting again. When closed properly, FEDS will tidy up the system resources and work properly the next time it is run.
During a month that has been identified as seasonally unoccupied (also referred to as non-operating), FEDS assumes zero occupancy, all lights are off (except exit signs), and the cooling system is shut down. Heating is operated at a reduced level generally for the purpose of preventing the pipes from freezing (temperature kept at low setpoint specified by the unoccupied season thermostat setting). General plug loads are assumed to be non-operational, as are most motors (although this may be overridden by specifying monthly motor load factors).
Unoccupied hours or day types of occupied months are those periods during which there is reduced occupancy of the building. These are referred to as low occupancy periods in FEDS. For a typical commercial facility this might occur during the night and on weekends. A small number of occupants might be present (though less than during normal operating hours), and all energy systems remain active although they may operate at reduced levels. The operation of HVAC, lighting, plug loads, and motors are all controlled by inputs such as thermostat setpoints (enabling temperature setback), ventilation control mode, and utilization/load factors.
Full 24-hour occupancy can be specified for any day type by entering the same start and end hours (except 0 and 2400). For unoccupied day types enter 0 for both start and end times (or leave them blank). Note: if you do not specify occupancy hours, they will remain blank and FEDS will model the buildings as though they are unoccupied (reduced occupancy). Shortcut buttons are available on the standard occupancy inputs screen to make specifying continuously occupied and unoccupied day types easier.
The best way to check the accuracy of a model is to run FEDS without optimization and compare the annual consumption estimated by FEDS to actual metered data. To do this, go to "Exclude Building Sets" from the "Optimization" option on the "Simulation" screen. Make sure the "Pick Building Sets" method is selected then press the "Select All" button on the left side of the screen (under the list of building sets). After saving, go back and run FEDS. This will take from a few seconds to a couple minutes for FEDS to run the baseline load and consumption calculations for the buildings. Alternatively, running with the analysis type set to "Calibration" will accomplish the same thing. Once complete, review the *.txs report for the case and check the following data:
General case and building inputs on the first five pages (for any obvious input errors)
Energy consumption data by fuel type (page 7)
Electric peak demand value and time of occurrence (page 8)
Annual energy consumption by fuel type and end use (page 10)
Do not expect these to be identical to the metered data—this is a model representation of your buildings and even if extremely precise, will vary due to discrepancies related to actual vs. average weather, human behavior, and more. Therefore, achieving consumption values from FEDS that are within 10-15% of actual values suggests a reasonably accurate model. An experienced user who is knowledgeable about building energy systems and their interactions can successfully calibrate to a much tighter tolerance.
A useful rule of thumb is that a full FEDS optimization run will take a couple minutes per building set. However, run-time depends on a number of factors, including computing resources, processor speed, size, and complexity of the case. The more buildings, use areas, and technologies being analyzed, the longer the FEDS run will take. Additionally, the presence and number of central energy plants and thermal loops will also impact run-time.
Conversely, a calibration run of the same case and computer takes only a few seconds (with additional time to generate the reports). This is because all building sets are excluded from optimization to help focus on the baseline energy results and aid in focusing on model quality assurance and calibration processes.
Installing FEDS will require approximately 1.7 GB of hard disk space. It is also important to have enough free disk space for case files. We recommend another 10-30 MB for this depending on the number and size of site models.
While FEDS models motor energy use, demand, and interactions with the HVAC system quite well, it is not a substitute for the MotorMaster+ software. MotorMaster+ contains extensive motor management and analysis capabilities that are found in no other software program. FEDS recommends general categories and performance levels of motors based on what is currently available, but does not specify particular manufacturers or special features. It is recommended that results of motor analyses from FEDS be used in MotorMaster+ to further refine and specify motor purchase requirements.
For example, the effect of the affinity laws on fan motors can have a significant impact in degrading the efficiency of an energy-efficient motor if it has less slip than the original motor. While it is true that many energy-efficient motors run faster than their standard efficiency counterparts, there are typically energy-efficient motors available with a full-load rpm equivalent to that of the motor it is replacing. FEDS does not account for the effect of speed on energy consumption in centrifugal loads, but assumes the user can find a motor with an equivalent slip as their current motor. MotorMaster+ is an invaluable tool to help users assess the impact of speed on energy consumption and finding the right motor for a given application.
inking two distinct building sets together allows greater flexibility in modeling complex building geometries or uses. Linked buildings are designed to model two buildings that share a common wall or are stacked on top of one another. Specifying that the buildings are linked directs FEDS to automatically (based on the geometry information for each building) determine the wall area (or roof/ceiling area) that is shared, and thus not exposed to exterior conditions. It essentially calculates the portion of each buildings shell that is an adiabatic surface (i.e., does not experience conductive heat transfer) and does not receive solar gains. It uses this information in load calculations to appropriately account for the impact of the buildings being connected. There are some rules, however, that must be satisfied in order to link building sets. First, both sets must contain the same number of buildings so that a direct one-to-one linking is achieved. Second, both sets must have the solar normalization turned off (calculate solar gains by facing direction). Also, FEDS currently does not model cantilevered buildings so for top/bottom linking, the N/S and E/W lengths of the top building must not be greater than the corresponding lengths of the bottom building.
The blue arrows indicate inputs that are required for FEDS to run. If any of these cells do not have a value provided, FEDS will not be able to run and will produce an alert either upon saving a screen or updating inferences. Once a valid input value has been provided and saved, the blue arrow will disappear.
The lock symbol that appears next to many of the input cells indicates the value is inferable by FEDS and does not require an input. An open lock icon means the value is not locked and may be changed by FEDS when inferences are updated. The closed lock symbol represents inputs whose value is locked and protected from being changed when inferences are updated. A user may lock a value by either entering a value into one of these cells, or by clicking on an open lock symbol to lock the value that is currently present in the cell.
Input cells that do not have an icon next to them are for values not absolutely required for FEDS to run but are highly recommended. Values, such as the fuel price data and occupancy hours are extremely important (yet a value may not be required for each fuel or day type). Others, such as the energy consumption inputs and building/technology identifications, are not used by FEDS except for reporting and aiding the user in understanding the output.
In FEDS MBtu signifies Million British Thermal Units. Throughout the program, the 'M' prefix represents million or 106 (MW, MBtu), while 'k' represents thousand or 103 (kWh, kBtu).
Prototype buildings in FEDS are modeled as basic rectangular blocks, with the actual geometry calculated based on the total floor area, number of floors, floor-to-floor height, and aspect ratio. However, additional geometries can be modeled by using the linked building approach or through the advanced geometry inputs, which allow modification to underlying parameters including window/wall/roof/floor areas and conditioned air volumes.
Variable occupancy is an improved approach to the seasonal occupancy option which allows users to specify that certain months are non-operating (e.g., schools may be shut down over summer break). Variable occupancy also offers greater flexibility by allowing users to specify the percent of days within specific months which follow the general occupancy and operation schedule defined in the standard occupancy inputs. One hundred percent indicates the building or use area operates all days of that type during the month according the standard schedule. Zero percent indicates the building (use area) is either non-operating (shut down) or in a low occupancy state (occupied at the low occupancy and equipment use level) for all days of that type during the month. For any value between 0% and 100%, FEDS will multiply that value by the actual number of days of that type in the month and model the resulting number of days (rounded to the nearest whole day) as operating according to the standard schedule. The remainder of the days of that type in the month will be deemed either non-operating or at low occupancy (depending on the selection of non-operating period status type). As a convention, FEDS will model the first X days in the month as occupied and operating to the standard schedule, and the remaining days of that type in the month as non-operating or at low occupancy. The variable occupancy capability provides significant modeling flexibility and is particularly useful in modeling occupancy and building operation that varies within the course of a month, such as for National Guard or Reserve buildings that may only be heavily occupied on certain weekends through much of the year.
Another option for even greater control over building and use-area operation and occupancy (for each hour of the year) is also available. Contact FEDS Support for more information if interested in using this approach.
The utilization factor represents the percentage of time during a particular period that the motor is operating. The load factor indicates the typical operating output of the motor as a percentage of rated output. For example, a 10-horsepower motor driving a 6-horsepower load and operating 50% of the time would have a load factor of 60% and a combined utilization/load factor of 30%.
FEDS allows the user to specify this information separately for occupied and unoccupied hours, either constant over the year, or varying from month to month. FEDS uses these values to calculate the hours of operation, and hence the consumption, and demand implications of each motor record. FEDS also calculates the heat output of the motors and its impact on the HVAC system.
The advanced geometry inputs allow for more flexibility in modeling non-standard building geometries compared to the linked building approach. When accessing the advanced geometry inputs, the user may specify or alter a number of geometric parameters for each zone of the building to customize the resulting model. For example, the exterior wall areas and window areas can be specified for the north, east, south, and west sides of each zone. Additionally, roof, floor, footprint areas, exterior perimeter length, and conditioned air volume can be specified for each zone. These adjustments provide users with the ability to model a number of more complex geometries, such as individual parts of a strip mall complex or varying window fractions for different sides of a building, with greater accuracy than through other means. The option can be accessed via the button on the regular geometry inputs screen.
Many motors in use today are oversized for the load they are driving, and some are grossly oversized. In such situations, the motor is driving a load equal to only a fraction of its rated capacity, and if too low the operating efficiency of the motor may suffer. Most importantly, when it's time to replace the motor, purchasing a motor with far excess capacity for its load will cost much more than a properly sized motor. Why spend more than necessary for the same (or even worse) level of service? FEDS understands t many motors may be over- (or under-) sized and allows the user to specify the required capacity of a motor, if known. FEDS will use the required capacity in order to select a replacement motor of the proper size and base its performance and cost calculations accordingly.
Solar normalization is used when the orientation of a single building is unknown, does not align with N/S/E/W directions, or when there are multiple buildings of differing orientations in a building set. It can be used to avoid biasing the solar gains calculation by normalizing the exterior wall, window, and roof areas, such that the resultant loads are roughly the average of two buildings: one with an east/west orientation and one with a north/south orientation. FEDS can be set to "ignore facing directions" to use solar normalization.
The aspect ratio is used to define the geometric orientation of the buildings in a building set. It is a ratio of length to width and is calculated by dividing the typical north-facing length by the typical east-facing length.
Motor inference data and an extensive list of replacement motors (including performance and cost data) have been compiled from the MotorMaster+ software's extensive database of three-phase motors. MotorMaster+ was developed under the U.S. Department of Energy's Motor Challenge Program by the Washington State University Cooperative Extension Energy Program.
No. All occupancy hours must be specified by the user. Failing to do so will indicate to the model that the building is operating in the unoccupied mode each day during the week.